Description
Model: GY-Oasis-B418LP
The liquid-cooled energy storage battery cabinet adopts an advanced independent liquid cooling control scheme and temperature uniformity control strategy for each cabinet, with a cell temperature difference of less than 3℃, further improving cell consistency and extending cell life. The modular design makes parallel operation more flexible and has higher energy density, significantly improving the economy, safety, and ease of construction of energy storage projects.
| DC battery parameters | |
| Cell type | LFP314Ah |
| Battery PACK Configuration | 52.25kWh/1P52S |
| PACK protection level | IP65 |
| Battery system configuration | 417.99kWh/1P416S |
| System rated voltage | 1331.2Vdc |
| Voltage range | 1164.8-1497.6V |
| AC side parameters | |
| AC rated power | 125kW |
| AC maximum power | 137.5kW (for 1 minute) |
| Alternating current distortion rate | ≤3% |
| DC component | <0.5%olpn |
| Rated voltage of power grid | 400Vac/3P+N+PE |
| Power factor adjustable range | -1~1 |
| Rated power grid frequency | 50Hz/60Hz |
| System parameters | |
| Maximum system efficiency | ≥89% |
| Charge/discharge rate | 0.5P |
| Depth of discharge | 95% |
| Loop count | ≥8000 times |
| Charge/discharge switching time | <100ms |
| Communication interface | Ethernet/RS485 |
| Protection level | IP55 |
| Cooling method | Active liquid cooling |
| Operating temperature | -25~55℃ |
| relative humidity | 0~95%RH non-condensing |
| noise | ≤75dB |
| altitude | ≤2000m (operation at reduced capacity above 2000m) |
| Fire protection system | PACK-grade aerosol + space-grade aerosol fire suppression + water fire extinguishing interface |
| System dimensions (width * depth * height) | 1250*1450*2250(mm) |
| weight | 3800Kg |
| Meets standards | GB/T 36276, GB/T 34120, GB/T34131, UN38.3, IEC62619, UL1973, UL9540, CE-EMC |









Reviews